Skip to content

LTE communicator for fire alarm control panels G17F

Front of the TRIKDIS G17F communicator, with an antenna connector on top and NETWORK, DATA, POWER and TROUBLE indicator labels. The case is marked 9–32 VDC, 0.1 A max. The bottom terminals are labeled, left to right: +DC, −DC, 1 IN, 2 IN, COM, 3 I/O, 4 I/O, COM, 5 I/O, 6 IN, A RS485 and B RS485.

1. Description

Communicator G17F meets the requirements of standard EN 54-21:2006.

The product complies with the performance requirements of EN54-21 standard Annex A for type 1 transmission system type.

Communicator G17F Certificate No: 1922-CPR-1974. Fire detection and fire alarm systems. Alarm transmission and fault warning routing equipment.

The product is certified by notified product certification body: No.1922 "Dedal", Nesebar Mladost str. 50, Bulgaria, 8230

Trikdis technical support contacts: support@trikdis.lt, +37067422877

The G17F is used for transmitting fire alarm control panel messages via cellular network.

Principle of operation. When an input (zone) of the communicator is violated, the G17F will transmit an event message to the Central Monitoring Station’s receiver or to the Protegus2 app using mobile internet. It can also send SMS messages and make phone calls. The communicator is available with 2G or 4G modems.

1.1 Features

Messages to the security company

  • Sends event information to TRIKDIS software and hardware receivers, which work with any monitoring software.

  • Can send events to SIA DC-09 receivers.

  • If connection via the main channel is lost, the messages are automatically sent to a backup receiver.

  • Can report events to the Central Monitoring Station using SMS messages. Extremely useful because it works even when IP connectivity is disrupted in the mobile operator’s network.

  • Cellular network jamming recognition.

  • Can simultaneously report events to the Central Monitoring Station and work with the Protegus2 app. It is possible to set priority for sending events to the Central Monitoring Station.

  • Event messages are sent in Contact ID codes.

Messages to users

  • Calls selected phone numbers (up to 8 users).

  • Sends SMS messages about events.

  • “Push” and special sound event notifications using the Protegus2 application.

Remote control of outputs

  • Via Protegus2 app.

  • By calling the device‘s phone number.

  • Via SMS messages.

Settings and installation

  • Quick and easy installation.

  • Device configuration either using an USB cable or remotely using TrikdisConfig software.

  • Remote updating of firmware.

  • Two access levels (types of accounts) for setting parameters: for the installer and for the administrator.

Inputs and outputs

  • 3 inputs, selectable type: NO, NC, EOL (4,7 kΩ, 10kΩ).

  • 3 double purpose I/O terminals that can be set as input (IN) or output (OUT) terminals. Selectable input types: NO, NC, EOL (4,7 kΩ, 10kΩ).

  • RS485 bus for connecting iO series expander modules.

  • Using iO series expanders, the number of inputs (IN) or outputs (OUT) can be increased to 12.

1.2 Specifications

Parameter Description
GSM/​GPRS modem frequencies 850 /​ 900 /​ 1800 /​ 1900 MHz
LTE modem frequencies 700 /​ 800 /​ 900 /​ 1800 /​ 2100 /​ 2600 MHz
Power supply voltage 9-32 V DC
Current consumption 100 mA
Transmission protocol TRK, SIA DC-09_2007, SIA DC-09_2012
Encryption key 6 symbol encryption key.
Connection to CMS TCP/​IP or UDP/​IP, SMS
Event codes Contact ID codes.
Memory Up to 60 messages.
Inputs and outputs 3 inputs, can be set as NO, NC, EOL (4,7 kΩ, 10kΩ) type. /​ 3 double purpose terminals (IN/​OUT), can be set as NO, NC, EOL (4,7 kΩ, 10kΩ) type inputs or open collector (OC) type outputs with current up to 100 mA.
Event memory Up to 1000 events.
Configuration Remotely using TrikdisConfig software or locally using USB Mini-B. Remotely using SMS messages.
RS485 bus length Up to 100 m
Supported modules iO – expander module;​ /​ iO-WL - iO-MO – iO-WL radio wave transceiver;​ /​ iO-8 - expander module;​ /​ E485 – „Ethernet“ module;​ /​ W485(W17u) – WiFi module;​ /​ iO-LORA – expander module;​ /​ iO8-LORA – expander module;​ /​ PB-LORA – panic button;​ /​ REL-LORA – expander module;​ /​ INIM Smartline - fire alarm control panel;​ /​ NSC Solution – fire alarm control panel;​ /​ C-TEC Cast ZFP – fire alarm control panel. /​ Fire alarm control panel with ESPA 4.4.4 protocol.
Operating environment Temperature from -10 °C to +50 °C, relative air humidity – up to 80% at +20°C.
Dimensions 92 x 62 x 25 mm
Weight 80 g

1.3 Elements of the G17F communicator

  1. SMA connector for Cellular antenna.

  2. Indicator lights.

  3. Slot for removing top cover.

  4. Terminals for connecting wires.

  5. USB Mini-B connector for programming the communicator.

  6. SIM card holder.

G17F communicator, front view on the left and exposed circuit board on the right. Left: 1 SMA connector for Cellular antenna, 2 indicator lights, 3 slot for removing top cover. Right: 4 terminals for connecting wires, 5 USB Mini-B connector for programming the communicator, 6 SIM card holder.

1.4 Purpose of terminals

Terminal Description
+DC Power supply terminal (9 - 32 V DC positive terminal)
-DC Power supply terminal (9 - 32 V DC negative terminal)
1 IN 1st input terminal, selectable type: NO, NC, EOL (10 kΩ default setting)
2 IN 2nd input terminal, selectable type: NO, NC, EOL (10 kΩ default setting)
COM Common (negative) terminal
3 I/​O 3rd double purpose terminal (IN/​OUT), can be set as input of selectable type NO, NC, EOL (10 kΩ default setting) or open collector (OC) type output with current up to 100 mA
4 I/​O 4th double purpose terminal (IN/​OUT), can be set as input of selectable type NO, NC, EOL (10 kΩ default setting) or open collector (OC) type output with current up to 100 mA
COM Common (negative) terminal
5 I/​O 5th double purpose terminal (IN/​OUT), can be set as input of selectable type NO, NC, EOL (10 kΩ default setting) or open collector (OC) type output with current up to 100 mA
6 IN 6th input terminal, selectable type: NO, NC, EOL (10 kΩ default setting)
A RS485 RS485 bus for connecting iO expanders, INIM Smartline fire control panels, NSC Solution fire control panels, C-TEC Cast ZFP fire control panels, fire control panels with ESPA4.4.4 protocol, and E485 and W485 modules.

1.5 LED indication of operation

Indicator Light status Description
Network Off Not connected to Cellular network
Green solid and yellow blinking The communicator is connected to Cellular network. Sufficient Cellular signal strength level for GPRS is 5 (five yellow flashes) and 3 for 4G (three yellow flashes).
Data Green solid Message is being sent
Yellow solid There are unsent events in the data buffer
Power Green blinking The power supply voltage is sufficient
Yellow blinking The power supply voltage is insufficient
Green and yellow blinking Configuration mode is on
Trouble Off No operational problems
1 blink No SIM card inserted
2 blinks The PIN code of the SIM card is incorrect
3 blinks Unable to connect to Cellular network
4 blinks Unable to connect to the IP receiver using the primary channel
5 blinks Unable to connect to the IP receiver using the backup channel
6 blinks Internal clock of the G17F is not set
7 blinks Insufficient power supply voltage
9 blinks Problems with the connection to the RS485 module

1.6 Components necessary for installation

Before beginning installation, make sure that you have:

  1. A USB Mini-B type cable for configuration.

  2. At least 4-wire cable for connecting the communicator to the fire control panel.

  3. A flat-head 2,5 mm screwdriver.

  4. An external Cellular antenna if network coverage in the area is poor.

  5. An activated nano-SIM card (PIN code requests can be turned off).

  6. The manual of the fire control panel that the communicator will be connected to.

Order the necessary components separately from your local distributor.

2. Quick configuration using TrikdisConfig software

  1. Download the configuration software TrikdisConfig from www.trikdis.com (type “TrikdisConfig” in the search field) and install it*.*

  2. Remove the lid of the G17F using a flat-head screwdriver as shown below:

Three line drawings showing how to open the G16 casing with a flat-head screwdriver: prying open the front cover tab, then prying open the side latch, and a close-up of the internal USB Mini-B connector.

  1. Connect the G17F to the computer using a USB Mini-B cable.

  2. Launch TrikdisConfig. The program will automatically recognize the connected device and will automatically open the G17F configuration window.

  3. Click the Read [F4] button to see the current parameters of the G17F. If a window requesting the administrator or installer code opens, enter the 6-digit code.

Below we describe the settings you need to edit to make the controller send events to the Protegus2 app or to the Central Monitoring Station (CMS).

2.1 Settings for connecting to Protegus2 app

In the “Users & Reporting” window, “Cloud application” settings group:

TrikdisConfig G17F configuration, Users & Reporting window. In Cloud application, Enable cloud service is checked and Cloud Access Code shows the example code 123456.

  1. Tick the box Enable cloud service.

  2. Change the Protegus Cloud access Code if you want users to be asked to enter it when they add the system in the Protegus2 app (default password – 123456).

In the “System options” window, “SIM” settings group:

TrikdisConfig G17F configuration, System Options window. In the SIM group, callout 3 highlights SIM card PIN 1234, and callout 4 highlights APN internet.

  1. Enter the SIM card PIN code.

  2. Change the APN. You will find the APN on the SIM operator’s website. “Internet” is universal and works in the networks of most operators.

In the “Zones” window:

TrikdisConfig G17F configuration, Zones window. The Prot. notification boxes are checked for Zones 1 through 6.

  1. Tick the boxes if you want users to receive notifications to Protegus2 about changes in zone states.

In the “PGM” window:

TrikdisConfig G17F configuration, PGM window. PGM 1 uses G17F 4 I/O; PGM 2 and 3 are set to Disable. The Prot. notification boxes are checked for all three rows.

  1. Tick the boxes if you want users to receive notifications to Protegus2 about changes in PGM output states.

In the “System events” window:

TrikdisConfig G17F configuration, System events window. The Prot. notification boxes are checked for Low power, Periodic test, RS485 fault, GSM jamming and Start IP event.

  1. Tick the boxes if you want users to receive notifications to Protegus2 about changes in the communicator’s internal event states.

After finishing configuration, click the Write [F5] button and disconnect the USB cable.

Note

See chapter 5 "Description of TrikdisConfig windows" to find more about other G17F settings in TrikdisConfig.

2.2 Settings for connecting to Central Monitoring Station

In the “System Options” window:

TrikdisConfig G17F configuration, System Options window. Highlighted fields are Object ID 0001, SIM card PIN 1234, and APN internet.

  1. Enter the Object ID (account) number provided by the Central Monitoring Station (4 characters, 0-9, A-F. Do not use FFFE, FFFF Object ID).

  2. Enter the SIM card PIN number.

  3. Change the APN. You will find the APN on the SIM operator’s website. “Internet” is universal and works in the networks of most operators.

In the “Reporting to CMS” window:

TrikdisConfig G17F configuration, Reporting to CMS window. The primary channel shows Communication type Disabled, Domain or IP 0.0.0.0, Port 0, Protocol TRK, and highlighted Encryption Key 123456. The backup channel shows the same values, including Encryption Key 123456. Backup channel 2 has an empty Phone number field.

  1. Communication type – choose a communication type (we do not recommend using SMS for the primary channel).

  2. Domain or IP – enter the receiver’s domain or IP address.

  3. Port – enter the receiver’s network port number.

  4. Protocol – choose which transmission protocol should be used for sending messages: TRK (to TRIKDIS receivers), DC-09_2007 or DC-09_2012 (to universal receivers).

  5. Encryption Key – enter the receiver’s encryption key.

Note

If you want to set connection to the Central Monitoring Station via SMS messages, you only need to set the Encryption key and Phone number. SMS messages can be received by TRIKDIS central monitoring station IP/SMS receiver RL14, multi-channel receiver RM14 and SMS receiver GM14. / If you chose DC-09 as the transmission protocol, additionally enter the object, line and receiver numbers in the Settings setting group of the "Reporting to CMS" window.

  1. (Recommended) Configure the Backup channel settings.

  2. (Recommended) Enter the Backup channel 2 phone number.

After finishing configuration, click the Write [F5] button and disconnect the USB cable.

Note

See chapter 5 "Description of TrikdisConfig windows" to find more about other G17F settings in TrikdisConfig.

3. Wiring schematics, installation and turning on the system

3.1 Fastening

  1. Before installing the system, make sure that Cellular signal strength is sufficient in the place where the G17F will be mounted.

  2. Remove the top cover, pull out the contact terminal blocks.

  3. Remove the board.

  4. Fasten the base of the casing in the desired place using screws.

  5. Reinsert the board and the contact terminal blocks.

  6. Screw on the Cellular antenna.

  7. Insert a nano-SIM card. The SIM card must be registered to a Cellular network and services must be enabled and functional, i.e. the card must be able to call, send and receive SMS messages, have enabled mobile data. Ask your SIM card’s mobile network operator how to enable desired services.

Two line drawings showing the CG17 circuit board with a circled tab on the left edge to release it from the casing, and the rear casing with two circled screw mounting holes.

Drawing of a nano-SIM card being inserted from the right into the SIM card holder on the G17F circuit board.

Note

Ensure that the SIM card is activated. / Ensure that mobile data is enabled if you are going to use connection via IP channel or Protegus2 app. / If you want to avoid entering the PIN code in TrikdisConfig, insert the SIM card into a phone and disable the PIN code request function.

  1. To configure the G17F remotely, insert a SIM card with disabled PIN code requests. Turn on the communicator’s power supply. If the G17F was not configured using TrikdisConfig and Protegus service was not enabled, send the SMS message: CONNECT  123456  PROTEGUS=ON,APN=INTERNET

  2. Changing parameters remotely is detailed in chapter 6 “Setting parameters remotely”.

  3. Reattach the top cover.

3.2 Schematic for connecting the communicator to a fire control panel

If you want to monitor the status of the fire alarm panel, connect its corresponding outputs to the G17F inputs. The outputs (PGM1, PGM2, PGM3) of the fire panel must be configured as panel status outputs (Alarm, Trouble, etc.).

Wiring diagram: fire control panel to G17F. Power: panel +24 V to +DC, GND to -DC. Status outputs: PGM1 to 1 IN, PGM2 to 2 IN, PGM3 to 6 IN, with their returns connected to COM. Each PGM circuit has a 10k resistor in parallel between its input line and COM return.

3.3 Connection diagram of the ESPA4.4.4 fire control panel and the G17F communicator

Wiring diagram: G17F to ESPA4.4.4 fire panel. Power: G17F +DC to ESPA4.4.4 +24V, -DC to 0V. RS485: G17F A to ESPA4.4.4 A, B to B.

G17F communicator settings using TrikdisConfig when connected to the ESPA4.4.4 fire panel.

  1. Choose the ESPA4.4.4.

  2. Select the interface baud rate.

  3. The data transmission parameters of the G17F communicator and the fire panel must be the same.

TrikdisConfig G17F configuration, Modules window. RS485 module 1 is set to ESPA 4.4.4 protocol. ESPA 4.4.4 interface settings show Baudrate 9600, 8 bits, parity None, 1 stop bit and Delay 40 mS.

  1. Enter phone numbers of users who should get messages from the G17F.

TrikdisConfig G17F, Users & Reporting window. Callout 4 highlights user 1: Name IT, a telephone number, with ACK and FW checked.

  1. If you want the user to receive messages (or calls) about events, tick the SMS (or Call) box

TrikdisConfig G17F configuration, System events window, SMS & Call reporting tab. For User 1, the ESPA 4.4.4 text event has SMS checked and Call unchecked.

  1. Configure the communication channel if messages should be sent to the CMS receiver. Event messages are transmitted using the SIA DC-09 protocol.

TrikdisConfig G17F, Reporting to CMS window. Callout 6 highlights Primary channel settings: Communication type Disabled, Domain or IP 0.0.0.0, Port 0, Protocol TRK, Phone number blank, and Encryption Key 123456.

Test the system. Activate the fire alarm and check that G17F messages are sent to the CMS (central monitoring station) and to Protegus2.

3.4 Connection diagram of the NSC Solution fire control panel and the G17F communicator

Wiring diagram: G17F to NSC Solution. Power: +DC to +24V (+24 V), -DC to 0V. RS485: A to A, B to B.

G17F communicator settings using TrikdisConfig when connected to the NSC Solution fire panel.

  1. Choose the „NSC Solution“.

  2. The “NSC slave address” must not match the addresses of the connected fire panel modules.

TrikdisConfig G17F, Modules window. Callout 1 highlights NSC Solution in RS485 modules row 1, named Expander ID1. Callout 2 highlights NSC slave address 10.

  1. Enter phone numbers of users who should get messages from the G17F.

TrikdisConfig G17F, Users & Reporting window. Callout 3 highlights user 1: Name IT, a telephone number, with ACK and FW checked.

  1. Users will get SMS messages and phone calls about events that are ticked. You can add additional CID event codes in the CID column. You must enter SMS text messages next to new codes. If you want the user to receive messages (or calls) about events, tick the SMS (or Call) box.

TrikdisConfig G17F, Users & Reporting, SMS for Panel events tab. Callout 4 highlights User 1: SMS checked and Call unchecked for the 16 displayed events, from E110 Fire alarm through R373 Fault restore.

  1. Configure the communication channel if messages should be sent to the CMS receiver.

TrikdisConfig G17F, Reporting to CMS window. Callout 5 highlights the Primary channel fields: Communication type Disabled, Domain or IP 0.0.0.0, Port 0, Protocol TRK, Phone number blank, and Encryption Key 123456.

After setting up the G17Fcommunicator, turn on power supply the fire control panel. Wait for the fire control panel software to load. It is necessary to scan the modules connected to the RS485 bus on the fire control panel. On the fire control panel, press: PROG.>INSTALLER>(Enter the installer code) 00000 OK>(Select) SETTINGS>ENTER>(Select) SCAN RS485>ENTER. Wait for the scan to complete. Return to the main screen by pressing “CANCEL“ twice.

Test the system. Activate the fire alarm and ensure that the G17F sends messages to the central monitoring station and Protegus2.

3.5 Connection diagram of the INIM Smartline fire control panel and the G17F communicator

Wiring diagram: G17F to INIM Smartline. Power: +DC to 13 +24 (+24 V), -DC to 16 GND. RS485: A to 15 +RS485, B to 14 -RS485. The diagonal wires cross without joining.

Slave mode must be set for the INIM Smartline panel when it is connected to the G17F communicator via RS485 bus.

SmartLeague, RS485 Bus Programming window. Under Master/Slave Settings, Configure as Slave is selected and Assign address is 1.

Note

You cannot connect the G17F using the RS485 bus if repeaters are connected to the INIM Smartline panel. / If the G17F communicator is connected to the RS485 bus of the INIM Smartline fire alarm panel, the communicator's iO expansion modules are not supported.

Setting up communicator parameters for operation with the INIM Smartline fire control panel.

In the “Modules” window:

TrikdisConfig G17F, Modules window. Callout 1 highlights Inim Smartline in RS485 modules row 1, named Expander ID1.

  1. Choose the Inim Smartline module.

In the “Users & Reporting” window:

TrikdisConfig G17F, Users & Reporting window. Callout 2 highlights user 1: Name IT, a telephone number, with the ACK and FW boxes checked.

  1. Enter phone numbers of users who should get messages from the G17F communicator.

TrikdisConfig G17F, Users & Reporting, SMS for Panel events tab. Callout 3 highlights User 1: SMS checked and Call unchecked for the first 16 events, from E110 Fire alarm through R373 Fault restore; both boxes are unchecked for row 17, E000.

  1. Users will get SMS messages and phone calls about events that are ticked. You can add additional CID event codes in the CID column. You must enter SMS text messages next to new codes. If you want the user to receive messages (or calls) about events, tick the SMS (or Call) box.

  2. Configure the communication channel if messages should be sent to the CMS receiver.

TrikdisConfig G17F, Reporting to CMS window. Callout 4 highlights the Primary channel fields: Communication type Disabled, Domain or IP 0.0.0.0, Port 0, Protocol TRK, Phone number blank, and Encryption Key 123456.

Test the system. Activate the fire alarm and ensure that the G17F sends messages to the central monitoring station (CMS) and Protegus2.

3.6 Connection diagram of the C-TEC Cast ZFP fire control panel and the G17F communicator

Wiring diagram: G17F to C-TEC Cast ZFP. Power: +DC to +24V (+24 V), -DC to 0V. ABUS RS485: A to A, B to B.

G17F communicator settings using TrikdisConfig when connected to the C-TEC Cast ZFP fire panel.

  1. Choose the C-TEC Cast ZFP fire control panel.

TrikdisConfig G17F, Modules window. Callout 1 highlights C-TEC Cast ZFP in RS485 modules row 1, named Expander ID1.

  1. Enter phone numbers of users who should get messages from the G17F communicator.

TrikdisConfig G17F, Users & Reporting  Users. Callout 2 highlights user 1, named IT, with a telephone number and the ACK and FW boxes checked.

  1. Users will get SMS messages and phone calls about events that are ticked. You can add additional CID event codes in the CID column. You must enter SMS text messages next to new codes. If you want the user to receive messages (or calls) about events, tick the SMS (or Call) box.

TrikdisConfig, Users & Reporting  SMS for Panel events. For User 1, the visible events have SMS checked and Call unchecked; the table pairs CID codes with SMS text, including E110 and Fire alarm.

  1. Configure the communication channel if messages should be sent to the CMS receiver.

TrikdisConfig, Reporting to CMS  Primary channel. Callout 4 highlights Communication type Disabled, Domain or IP 0.0.0.0, Port 0, Protocol TRK, a blank Phone number field, and Encryption Key 123456.

Install the ZFPtools program on your computer. Run the ZFPtools program. Turn on the power supply of the fire control panel. Wait until the fire panel software is loaded. Connect the fire panel to the computer using a USB2.0 A-B cable.

  1. Open the "Node View" tab.

ZFP Programming Tools, Site Details window. The Node View tab is highlighted for selection.

  1. Download the fire panel settings to your computer.

ZFP Programming Tools, Node View for Panel 1. The Retrieve All Data button is highlighted.

  1. Enter the code (default code – 4444).

  2. Click „OK“.

ZFP Programming Tools, Panel Log In window. Enter Access Level 3 Code appears above four empty code boxes; the green check button confirms the entry.

  1. Select „BMS Interface“.

  2. Click on the free icon.

ZFP Programming Tools, Node View  Devices. BMS Interface is selected in the Device Palette, and the Edit Devices button is highlighted.

  1. Click „Edit Devices“.

ZFP Programming Tools, Node View  Devices. A BMS Interface occupies device slot 16, and the Edit Devices button is highlighted.

  1. In the “Device” tab, enter the system name.

ZFP Programming Tools, Node View  Devices  Device Properties for device 16. On the Device tab, Name is FIRECOM and Device Type is BMS Interface.

  1. In the “Properties” tab, enter the system name.

  2. Specify the “ABUS RS485” bus to which the G17F communicator is connected.

  3. Configure messages.

  4. Write the settings to the fire panel.

ZFP Programming Tools, Device Properties for the BMS Interface. Name is FIRECOM; Connection is ABUS RS485; BAUD Rate is 57600; Response Timeout is 250; Max Retries is 5. Zone Disablements reports Zone; Input Group Disablements, Output Group Disablements and Group Actions report Group. The Send All Data button is highlighted.

  1. Enter the code (default code – 4444).

  2. Click „OK“.

ZFP Programming Tools, Panel Log In window. Enter Access Level 3 Code appears above four empty code boxes; the green check button confirms the entry.

The fire panel is programmed. Disconnect the cable from USB2.0 A-B of the fire panel.

Test the system. Activate the fire alarm and check that G17F messages are sent to the CMS (central monitoring station) and to Protegus2.

3.7 Schematics for connecting inputs

The communicator has six (1IN – 6IN) input terminals (three terminals are dual purpose IN/OUT) for connecting NO, NC, EOL (4,7kΩ, 10 kΩ) type circuits. Default input setting – monitor an EOL type circuit. You can set a different input type in the TrikdisConfig window Zones.

Schematics of NO, NC, EOL type circuits:

3.7.1 Normally open (NO)

Input wiring diagram: normally open (NO) contact between COM and INx. Short - Alarm, Open - Restore.

3.7.2 Normally closed (NC)

Input wiring diagram: normally closed (NC) contact between COM and INx. Short - Restore, Open - Alarm.

3.7.3 Normally open with 10k end-of-line resistor (EOL10k)

Input wiring diagram: NO contact with a 10 k end of line resistor in parallel between COM and INx (EOL10k). Short - Alarm, Open - Alarm, 10k - Restore.

3.7.4 Normally closed with 10k end-of-line resistor (EOL10k)

Input wiring diagram: NC contact in series with a 10 k end of line resistor between COM and INx (EOL10k). Short - Alarm, Open - Alarm, 10k - Restore.

3.8 Schematic for connecting iO series expander modules

If the communicator needs more inputs IN or outputs OUT, connect a wired or wireless TRIKDIS iO series input and output expander.

Wiring diagram: G17F to iO-MOD, iO-WL and iO modules. G17F to the two shown iO-MOD units: DC+ to +DC by red wire, DC- to -DC by blue wire, A RS485 to A RS485 by black wire, B RS485 to B RS485 by white wire; 12-28V supply, up to 4 iO-MOD modules. Each iO-MOD has a wireless connection to an iO-WL, up to 300 m. Upper iO-WL to iO: A RS485 to A RS485 and B RS485 to B RS485, up to 300 m and up to 8 system expansion modules. Both have 12-28V supplies with -DC joined. Lower iO-WL has its own 12-28V supply.

3.9 Schematic for connecting an iO-8 expander module

If you need the communicator to have more IN inputs or OUT outputs, connect the iO-8 wired expander.

Wiring diagram: G17F to iO-8. G17F +DC to iO-8 +DC, -DC to -DC, A RS485 to A, and B RS485 to B.

3.10 Schematics for connecting LORA series expander modules

Schematics for connecting LORA modules.

Wiring diagram: G17F to RF-LORA. Power: +DC to +DC (+12 V), -DC to -DC. RS485: G17F A to RF-LORA A RS 485, B to B RS485. RF-LORA works wirelessly, up to 5000 m, with iO-LORA, iO-8-LORA, PB-LORA and REL-LORA. The illustrated iO-LORA and iO-8-LORA each have a separate 12-26V supply at +DC and -DC; PB-LORA and REL-LORA are also shown. REL-LORA has 100-230V AC at L and N.

3.11 Schematic for connecting the W485 WiFi module

G17F firmware version from 1.08. / The W485 module sends messages to the CMS (Central Monitoring Station) and to Protegus2 using a WiFi internet router. When WiFi connectivity is available, the G17F sends event messages via the W485 module. When WiFi connectivity is disrupted, the G17F sends messages via GPRS. When WiFi connectivity is re-established, the G17F returns to sending messages via W485. / Configuration of the W485 WiFi module to work with the G17F is described in chapter 5.5. „„Modules” window”. / You do not need a SIM card, when using the W485 with the G17F.

Wiring diagram: G17F to W485. Power supply (12 V DC, 0,5 A) to +DC and -DC of both, joined at junction dots. RS485 connection (up to 100 m): G17F A 485 to W485 A 485, B 485 to B 485.

3.12 Schematic for connecting the E485 “Ethernet” module

G17F firmware version from 1.08. / The E485 sends messages to the CMS (Central Monitoring Station) and to Protegus2 using a wired internet connection. Using the E485 with G17F, CMS and Protegus2 messages are sent over wired Internet and mobile Internet is not used. If a wired internet connectivity is disrupted, the G17F sends messages via the mobile Internet. When the wired Internet connectivity is re-established, G17F starts sending messages via E485. / Configuration of the E485 module to work with the G17F is described in chapter 5.5. „„Modules” window”. / You do not need a SIM card, when using the E485 with the G17F.

Wiring diagram: G17F to E485. Power supply (12 V DC, 0,5 A): +DC to +DC and -DC to -DC, each joined at a junction dot. RS485 connection (up to 100 m): G17F A 485 to E485 A 485, B 485 to B 485.

3.13 Turning on the communicator

To turn on the communicator, you must first provide a power source for the fire control panel. If the communicator is working properly, the following G17F indicator lights should turn on:

  • The “POWER” diode must be green solid (sufficient power supply voltage);

  • The “NETWORK” diode must be green solid and blink yellow when the communicator is connected to a network.

Note

Sufficient Cellular signal level - 5 (five yellow flashes of the "NETWORK" indicator). Sufficient 4G signal level - 3 (three yellow flashes of the "NETWORK" indicator). / If you count less than 3 yellow flashes of the "NETWORK" diode, the Cellular signal level is insufficient. We recommend choosing a different place for installing the communicator or using a more sensitive Cellular antenna. / If the indication is different, search for the explanation in chapter 1.4 "LED indication of operation". / If the G17F's indicator lights are completely inactive, check the power supply and connections.

4. Remote control

4.1 Adding the communicator to Protegus2 app

Using Protegus2, users can see the system’s state and receive notifications about system events.

  1. Download and launch the Protegus2 app or use the browser version www.protegus.app:

  2. Create a new account or log in with your user name and password.

Important

When adding the system to Protegus2 the G17F communicator must:

  1. Have an inserted and activated SIM card with the PIN code entered or disabled;

  2. Have Protegus service enabled. See 5.4 "Users & Reporting" window;

  3. Have the power switched on ("POWER" LED must be green solid);

  4. Be connected to a network (the "NETWORK" LED must be green solid and blink yellow).

  1. Click „Add new system” and enter the G17F’s “Unique ID” number. It can be found on the device and packaging sticker. After entering the unique ID, click the “Next” button.

Annotated screenshot of the Protegus2 app's "Scan QR code" screen with a callout pointing to the Unique ID/IMEI field explaining where to find the IMEI code, and a red box highlighting the QR code location on a sample product label below.

4.2 Configuration and control via SMS messages

1. Change the administrator password

To ensure safety, change the default administrator SMS password. Send an SMS message of the following format:

4.2.1 PSW 123456 xxxxxx

123456 Default administrator password
xxxxxx New 6-symbol administrator password
  1. Allow other users to control

Only phone numbers on the user list can control the system using SMS messages or phone calls. From an administrator phone, send SMS messages with other people’s phone numbers and names to allow them to control the system:

4.2.2 SETN xxxxxx PHONEx=+PHONENR#NAME

xxxxxx 6-symbol administrator password
x User’s number on the list. (If you write 1 as the user number, you will transfer your administrator’s rights to the other user.)
PHONENR User’s phone number
NAME User’s name

SMS command list

Command Data Description
INFO Request information about the communicator. Communicator type, IMEI number, serial number and firmware version will be included in the answer. / E.g.: INFO 123456
RESET Reset the device. E.g.: RESET 123456
OUTPUTx ON Turn on an output, “x” is the output number. E.g.: OUTPUT1 123456 ON
OUTPUTx OFF Turn off an output, “x” is the output number. E.g.: OUTPUT1 123456 OFF
OUTPUTx PULSE=ttt Turn on an output for a few seconds - “x” is the OUT output number, and “ttt” is a three-digit number that specifies pulse time in seconds. / E.g.: OUTPUT1 123456 PULSE=002
PSW New password Change password. E.g.: PSW 123456 654123
TIME YYYY/MM/DD,12:00:00 Set date and time. E.g.: TIME 123456 2025/05/09,10:23:00
TXTA Object name Specify an object name. E.g.: TXTA 123456 House
TXTE Z1= / ........ / Z12= Customize zone alarm SMS message text: Z1...Z12 – input zone number. / E.g.: TXTE 123456 Z1=ALARM in Zone1
TXTR Z1= / ........ / Z12= Customize zone restore SMS message text: Z1...Z12 – input zone number. / E.g.: TXTR 123456 Z1=Restore Zone1
RDR PhoneNR#SMStext Forward SMS messages to the specified number. The phone number must start with a "+" sign and the international country code.
RDR PhoneNR#SMStext E.g.: RDR 123456 +37061234567#forwarded text
ASKI Request SMS message about statuses of inputs IN. E.g.: ASKI 123456
ASKO Request SMS message about statuses of outputs OUT. E.g.: ASKO 123456
SETN PhoneX=PhoneNR#Name Add a phone number, username and assign it to user “x”. “x” is the phone number’s line on the list. The phone number must start with a "+" symbol and international country code. The phone number and username must be separated by a # symbol. E.g.: SETN 123456 PHONE5=+37061234567#JOHN
PhoneX=DEL Delete user’s phone number and name from the system. / E.g.: SETN 123456 PHONE5=DEL
UUSD *Uusd code# Send a UUSD code to the operator. E.g.: UUSD 123456 *245#
CONNECT Protegus=ON Connect to Protegus cloud service. E.g.: CONNECT 123456 PROTEGUS=ON
CONNECT Protegus=OFF Disconnect from Protegus cloud service. E.g.: CONNECT 123456 PROTEGUS=OFF
CONNECT Code=123456 Protegus cloud service code. E.g.: CONNECT 123456 CODE=123456
CONNECT IP=0.0.0.0:8000 Specify the main server’s connection channel’s TCP IP and Port. / E.g.: CONNECT 123456 IP=0.0.0.0:8000
CONNECT IP=0 For turning off the main channel. E.g.: CONNECT 123456 IP=0
CONNECT ENC=123456 TRK encryption key. E.g.: CONNECT 123456 ENC=123456
CONNECT APN=Internet APN name. E.g.: CONNECT 123456 APN=INTERNET
CONNECT USER=user APN user. E.g.: CONNECT 123456 USER=User
CONNECT PSW=password APN password. E.g.: CONNECT 123456 PSW=Password

4.3 Control PGM outputs using phone calls

Note

If no users have been added to the system, the first one to call the G17F will become the system administrator and will be the only one who can control the G17F using phone calls and SMS commands. / If you want to allow additional users to control the system using phone calls, add them with TrikdisConfig or give them the rights using SMS commands.

Perform these actions if you want to control a PGM output remotely:

  • The user must be allowed to control outputs OUT and the output OUT must have type “Remote control” assigned (using TrikdisConfig).

  • Call the number of the G17F’s SIM card. The G17F will answer the call and you can dial commands using the phone’s keypad (see the table).

Mobile phone keyboard command list

Keyboard buttons Function Description
[output no]*[state no]# Control selected output OUT Controls the specified PGM output. State: [0] – output turned off; [1] – output turned on; [2] – turned off for pulse time; [3] – turned on for pulse time; (pulse time is specified in the TrikdisConfig software, “PGM” table) [] – this symbol shows the end of the command. E.g. (turn on output 1): 11# E.g. (turn off output 1): 10# E.g. (turn on output 2 for Pulse time specified in the TrikdisConfig “PGM” table): 23#
# Retry entering the command If you made a mistake while entering the command, press # on the phone’s keyboard and enter the command again.

5. Description of TrikdisConfig windows

5.1 Description of TrikdisConfig status bar

Once the G17F is connected, TrikdisConfig will display information about the connected device in its status bar.

TrikdisConfig status bar for a connected G17F: Status Ready, bootloader 2.03, firmware 1.18, State USB and Role Administrator. IMEI/Unique ID and serial number fields are also shown.

Name Description
IMEI/​Unique ID Device’s IMEI number
Status Operational state
Device Device type (must show G17F)
SN Device’s serial number
BL Bootloader version
FW Device’s firmware version
HW Device’s hardware version
State Type of connection with the program (USB or remote)
Role Access level (shown after access code is approved)

When the Read [F4] button is clicked, the program will read and show settings currently saved on the G17F. With TrikdisConfig, set the required parameters using the following program window descriptions.

5.2 “System Options” window

TrikdisConfig System Options, System general tab. General settings show Object ID 0001, object name G17F, test period enabled at 1 day 0 hours, Time set to GSM modem, Clear Events after reset checked, Text language Baltic, suspend event reporting after 2 same events per 10 seconds, restore reporting after 1 minute, Low power voltage 24 volts and EOL resistor value 10k. SIM settings show PIN 1234 and APN internet. Time zone is enabled at +2 hours 0 minutes, with Daylight saving time checked.

“System general” tab “General” settings group

  • Object ID – if events are going to be sent to the CMS, enter the Object ID (4-symbol hexadecimal number, 0-9, A-F. Do not use FFFE, FFFF Object ID) given by the CMS.

  • Object name – the name given to the object that will be used in SMS messages sent to the user.

  • Test period - when the box is ticked, “Test” messages will be sent every set period.

  • Time set – choose a server to synchronize time with. If you choose “IP server”, time will be synchronized with the IP receiver’s time, if you choose “Cellular modem”, time will be synchronized with the GSM service provider’s server time.

  • Clear Events after reset – all unsent event messages will be deleted upon reset.

  • Text language – set the preferred language and the specific symbols of that language will be used in SMS messages.

  • You can Suspend event reporting when ... a number of same events per ... s happen.

  • Restore event reporting after ... – set the time after which suspending of event reporting will be cancelled. The time can be anywhere from 0 to 999 minutes.

  • Low power voltage – specify the power supply voltage (12 V or 24 V) that will be used for forming messages about insufficient power supply voltage.

“SIM” settings group

  • Enter the SIM card PIN code**.**

  • APN – network service provider’s mobile internet access point name. You must enter the APN if event messages will have to be sent to Protegus2 app or to the CMS via GPRS.

  • If required by the GPRS network service provider, enter the APN user name and password in the fields Login and Password.

“Time zone” settings group

  • Time zone – specify your country’s time zone. For example, if the communicator will be installed in Lithuania, enter +3.

  • Daylight saving time – if you check the box, the communicator's internal clock will be automatically switched to summer or winter time.

“Access” tab

TrikdisConfig System Options, Access tab. Access codes show Administrator Code 123456, SMS password 123456 and Installer Code 654321. Under Installer permissions, Object ID and SIM card are checked. Area Settings and the Users & Reporting, Modules, Zones, PGM, Reporting to CMS and System events menus are set to Editable.

Settings group “Access codes”

  • Administrator Code – gives full access to configuration functions (default code – 123456).

  • SMS password – password for remote control and programming via SMS messages (default code – 123456).

  • Installer Code – gives limited access to changing the communicator’s configuration (default code – 654321).

Settings group “Installer permissions”

The administrator can set which parameters can be changed by the installer.

5.3 “Reporting to CMS” window

TrikdisConfig Reporting to CMS window. Primary and Backup channels both show Communication type Disabled, Domain or IP 0.0.0.0, Port 0, Protocol TRK and Encryption Key 123456; their phone-number fields are blank. Settings show Return to Primary after 5 min, enabled IP Ping period 60 s and SMS Ping period 10 min, Backup reporting after 3 attempts, DNS1 8.8.8.8 and DNS2 8.8.4.4. SIA DC-09 fields show Object ID 0001, receiver No. 1 and line No. 1. The Backup channel 2 phone-number field is blank.

The communicator sends messages to the Central Monitoring Station using internet (IP) or SMS messages.

You can assign a backup channel to the primary channel. It will be used when connection via the primary channel is lost.

Messages sent to the Central Monitoring Station are encoded and password protected. To receive messages and forward them to monitoring software, a TRIKDIS receiver is required:

  • For IP messages – receiving program IPcom Windows/Linux, hardware IP/SMS receiver RL14 or multi-channel receiver RM14.

  • For SMS messages – hardware IP/SMS receiver RL14, multi-channel receiver RM14 or SMS receiver GM14.

Connection via SMS messages is extremely useful for the backup channel, because it works even when internet connectivity in the operator’s network is disrupted. Using SMS as the primary channel is not recommended.

Settings group “Primary channel”

  • Communication type – choose a method for connecting to the Central Monitoring Station’s receiver.

  • Domain or IP – enter the receiver’s domain or IP address.

  • Port – enter the receiver’s network port number.

  • Protocol – TRIKDIS IP receivers can receive messages sent in the TRK protocol, and SIA DC-09 protocols are used for IP receivers capable of receiving event messages sent in SIA DC-09 protocols.

  • Phone number – (only for SMS messages) enter the phone number of a TRIKDIS SMS receiver. The phone number must start with the country code (e.g.: 370xxxxxxxx).

  • Encryption Key – 6-digit message encryption key. The communicator’s encryption key must match the receiver’s encryption key.

Settings group “Backup channel”

Enable backup channel mode to allow messages to be sent using the backup channel if the connectivity is disrupted. Configure the backup channel using the same settings as described above.

Settings group “Settings”

  • Return to Primary after – time period after which the G17F will attempt to regain connection with the Primary channel.
  • IP PING period – sending period of internal PING signals for checking connectivity. These messages are sent only via IP channel. The receiver does not forward these signals to the monitoring software and thus does not overload the software. The monitoring software is only notified when the receiver does not receive a PING message from the device for a preset period of time.

By default, the receiver will send a “Connection lost” message to the monitoring software after a time period that is three times longer than the communicator’s PING sending period. E.g. if the IP PING period is 3 minutes, the receiver will send a lost connection message if it does not receive a PING for 9 minutes.

PING messages also keep an active connection session between the device and the receiver. An active session is required to configure and control the communicator remotely. We recommend setting the PING period to be no longer than 5 minutes.

  • SMS Ping reporting - period of sending a PING signal over the channel for sending SMS messages, min.. Check the box to enable communication channel and specify the time interval.

  • Backup reporting after – specify the number of unsuccessful attempts to send a message using the Primary channel. If the message fails to send after the specified number of attempts, the device will transmit using the Backup channel.

  • DNS1, DNS2 – (Domain Name System) server that specifies the domain IP address. It is used when a domain is specified in the connectivity channel’s Domain or IP field (instead of an IP address). Default setting - Google DNS server addresses.

The following settings are only shown when DC-09_2007 or DC-09_2012 protocol is chosen in the connectivity channel’s Protocol field.

  • Object ID in SIA DC-09 – enter the object number. If you chose the DC-09 protocol, the object number entered in this field will be used. You can enter the 3-16 symbol hexadecimal number given by the central monitoring station.

  • SIA DC-09 receiver No. – enter the receiver’s number.

  • SIA DC-09 line No. – enter the line number in the receiver.

Settings group “Backup channel 2”

  • Phone number - (only for SMS messages) enter the phone number of a TRIKDIS SMS receiver. The phone number must start with the country code (e.g.: 370xxxxxxxx).

5.4 “Users & Reporting” window

“Users” tab

TrikdisConfig Users & Reporting window, Users tab: the first user row is populated, with ACK and FW checked; the other visible rows are empty. In Cloud application, Enable cloud service is checked, Parallel reporting is unchecked, and a Cloud Access Code field is shown.

Settings group “Users & Reporting to User”

  • ID – user’s number on the list.

  • Name – user’s name. These names will be used in event SMS messages.

  • Tel number – the user’s phone number that will receive SMS messages. Numbers must be entered with the international code.

  • PGM – if the box is ticked, the user can remotely control outputs.

  • ACK – if the box is ticked, the G17F will send SMS messages with SMS answer text to the user after every received SMS command.

  • FWD – if the box is ticked, SMS messages received from non-system users will be forwarded to the user (e.g. SIM card account balance, random promotional messages, etc.).

Settings group “Cloud application”

  • Enable cloud service – enable Protegus service to allow the G17F to exchange data with the Protegus2 app and remotely configure the device using TrikdisConfig.

  • Parallel reporting – enable parallel message sending via the Primary channel and to Protegus2.

  • Cloud access code – 6-digit code for logging in to Protegus2 (default code - 123456).

“SMS answer texts” tab

TrikdisConfig Users & Reporting window, SMS answer texts tab: the SMS text matches each answer label shown—Command done, Wrong password, Wrong data and Wrong command.

Settings group “SMS answer texts”

  • Edit the answer texts to control commands sent via SMS messages in the column SMS text.

“SMS for Panel events” tab

TrikdisConfig Users & Reporting window, SMS for Panel events tab. For User 1, SMS is checked and Call is unchecked for these visible CID events: E110 Fire alarm, E118 Fire pre-alarm state, E380 Detector fault, E323 Line fault, E301 AC loss, E302 Low battery, E311 Missing battery, E305 Panel reset, E372 Zone short, E371 Zone open, E574 Zone disabled, R574 Zone enabled, E604 Test, E320 Sounder fault, R320 Sounder restore and R373 Fault restore. The final visible row, E000, has neither SMS nor Call checked.

This window will only be displayed if at least one user phone number has been added to the „Users & Reporting“ window*.*

  • Zn – event’s number on the list.

  • CID – event’s Contact ID code.

  • SMS text – event’s SMS message text.

  • User SMS/Call– choose how to inform users about every event – SMS message and/or call.

5.5 “Modules” window

TrikdisConfig Modules window, RS485 modules tab. An eight-row table lists module IDs 1–8 with names Expander ID1–Expander ID8; the first row's Module dropdown is open. Its visible choices are Not available, iO expander, iO-WL radio expander, iO-8 expander, Inim Smartline, E485 communicator, W485 (W17u) module, iO-LORA expander, iO8-LORA expander, PB-LORA Panic button, REL-LORA expander, NSC Solution, C-TEC Cast ZFP and ESPA 4.4.4 protocol.

Settings group “RS485 modules”

  • ID – module’s number on the list.

  • Module – choose the module being used (modules iO, iO-WL, iO-8, Inim Smartline, E485, W485, iO-LORA, iO8-LORA, PB-LORA, REL-LORA, NSC Solution, C-TEC Cast ZFP, ESPA 4.4.4) from the module list.

  • Serial No. – mandatory 6-digit number that can be found on the module’s casing and its packaging.

  • Name – you can give the module a name.

  • Firmware version – the firmware version will be shown when the G17F finds the connected module.

„W485 settings“ tab

TrikdisConfig Modules window, W485 settings tab: DHCP mode is checked; Static IP, Subnet mask and Default gateway each show 0.0.0.0; Wifi SSID name is TRIKDIS. In SIM parameters, Use dial and SMS when working over internet module is checked, while the other two options are unchecked.

WiFi module W485 (W17u) settings window „Communicator network settings“ settings group

  • DHCP mode – WiFi module’s mode for registering to network (manual or automatic). Check the box (automatic registration mode) and the WiFi module will automatically scan the network settings (subnet mask, gateway) and will be assigned an IP address.

  • Static IP – static IP address for when manual registering mode is set.

  • Subnet mask – subnet mask for when manual registering mode is set.

  • Default gateway – gateway address for when manual registering mode is set.

  • Wifi SSID name – name of the WiFi network that the W485 (W17u) will connect to.

  • Wifi SSID password - WiFi network password.

„SIM parameters“ settings group

  • Disable indication of the absence of a SIM card – checking the box will disable the indication of the absence of the SIM card in the G17F controller.

  • Use dial and SMS when working over internet module – checking the box will enable control of the communicator via call and SMS. If the field is not checked and there is a Wi-Fi network, then the call and SMS messages are not used. If the field is unchecked and there is no Wi-Fi network, then G17F can manage call and SMS messages. G17F will send SMS messages to the user.

  • Disable the use of SIM card mobile data – checking the box will disable the use of mobile data from the SIM card. Data will only be sent via module W485. If the Wi-Fi network is disconnected, G17F will store data in memory. After restoring the Wi-Fi network, the G17F will send the saved data via the Wi-Fi W485 module***.***

„E485 settings“ tab

TrikdisConfig Modules window, E485 settings tab: DHCP mode is checked, and Static IP, Subnet mask and Default gateway each show 0.0.0.0. In SIM parameters, Use dial and SMS when working over internet module is checked; Disable indication of the absence of a SIM card and Disable the use of SIM card mobile data are unchecked.

„Ethernet“ module E485 settings windows „Communicator network settings“ settings group

  • DHCP mode – „Ethernet“ module’s mode for registering to network (manual or automatic).

  • Static IP – static IP address for when manual registering mode is set.

  • Subnet mask – subnet mask for when manual registering mode is set.

  • Default gateway – gateway address for when manual registering mode is set.

„SIM parameters“ settings group

  • Disable indication of the absence of a SIM card – checking the box will disable the indication of the absence of the SIM card in the G17F controller.

  • Use dial and SMS when working over internet module – checking the box will enable control of the communicator via call and SMS. If the field is unchecked and there is internet, then SMS and calls are not used. If the field is unchecked and there is no Internet, then G17F can manage call and SMS messages. G17F will send SMS messages to the user.

  • Disable the use of SIM card mobile data – checking the box will disable the use of mobile data from the SIM card. Data will only be sent via module E485. If the internet disappears, G17F will store data in memory. When the Internet is restored, the G17F will send the saved data via the “Ethernet” E485 module***.***

5.6 “Zones” window

“Zones settings” tab

TrikdisConfig Zones window, Zones settings tab. Six zones use G17F inputs 1 IN, 2 IN, 3 I/O, 4 I/O, 5 I/O and 6 IN, respectively. Every row shows Definition 24_hours, Type EOL, checked CMS and Prot. boxes, Delay 400, CID Code 133, SIA E FA, SIA R FR and LOOP 99.

  • Zone No – zone’s number on the list.

  • Name - the zone can be given a name that will be used in SMS messages.

  • Input – choose which G17F or expansion module input IN to assign to a zone.

  • Definition – all zones are assigned the 24 hours definition. If this zone is violated, a message about the event is sent immediately.

  • Type – choose the type of circuit connected to the zone input IN from a list: NC – normally closed contact, NO – normally open contact, EOL – with a (4,7kΩ or 10 kΩ) resistor at the end of the circuit.

  • CMS – if the box is ticked, messages about zone events will be sent to the CMS (central monitoring station).

  • Prot. – if the box is ticked, notifications about zone events will be sent to Protegus2 app.

  • Delay – IN input zone reaction time in milliseconds.

  • CID Code – event’s Contact ID code.

  • SIA E – SIA Event code.

  • SIA R – SIA Restore code.

  • LOOP - the loop number is indicated in the SMS message.

“SMS & Call reporting” tab

TrikdisConfig Zones window, SMS & Call reporting tab: User 1 has SMS checked and Call unchecked for the visible zone Event and Restore rows. SMS texts include Zone 1 Alarm, Zone 1 Restore, Zone 2 Alarm, Zone 2 Restore, Zone 3 Alarm, Zone 3 Restore and Zone 4 Alarm.

This window will only be displayed if at least one user phone number has been added to the „Users & Reporting“ window*.*

  • Zn – zone number with an event identification word. Can be “Event” or “Restore”.

  • SMS text – description of the zone event that will be included in SMS event messages sent to users.

  • User SMS/Call – choose how to inform users about every zone event – via SMS message and/or call.

5.7 “PGM” window

“Outputs” tab

TrikdisConfig PGM window, Outputs tab: PGM 1 uses G17F 4 I/O; PGM 2 and 3 show Disable. All three rows show Output definition Remote Control, Pulse Time 20 s, Prot. checked, SIA E RC and SIA R RO.

  • PGM No – PGM output’s number on the list.

  • PGM output – assign outputs OUT of the G17F or of an external device to a PGM.

  • Output definition – select operational mode of an output OUT.

  • Pulse time, s – assign a desired OUT turn on duration from 0 to 9999 seconds.

  • CMS – if the box is ticked, messages about chosen events will be sent to CMS.

  • Prot. – if the box is ticked, output event notifications will be sent to Protegus2 app.

  • SIA E – SIA Event code.
  • SIA R – SIA Restore code.

“SMS & Call reporting” tab

TrikdisConfig PGM window, SMS & Call reporting tab: for User 1, PGM 1 Event has SMS text OUT1 ON and PGM 1 Restore has SMS text OUT1 OFF. SMS is checked and Call is unchecked for both rows.

This window will only be displayed if at least one user phone number has been added to the „Users & Reporting“ window

  • PGM – the number of output OUT and turn on/off event type (“Event” – output OUT turn on event and “Restore” – OUT turn off event).

  • SMS text – output OUT turn on/off event name that will be included in the event’s SMS message.

  • User SMS/Call – choose which users to inform via SMS message and/or call when an output OUT is turned on/off.

5.8 “System events” window

“Events” tab

TrikdisConfig G17F System events window, Events tab. Enabled events include Low power (CID 302), Periodic test (602), RS485 fault (333), GSM jamming (344) and Start IP event (700). The table also shows CMS and Prot. selections, SIA codes, loop numbers, and SMS event and restore text.

  • ID – event’s number on the list.

  • Event name – event name.

  • Enable – enable event recognition.

  • CMS – messages about chosen events will be sent to CMS.

  • Prot. – notifications about chosen events will be sent to Protegus2 app.

  • CID Code – event’s Contact ID code.

  • SAI E – SIA Event code.

  • SIA R – SIA Restore code.

  • LOOP - the loop number is indicated in the SMS message.

  • SMS event text – text of the event’s SMS message.

  • SMS restore text - text of the event’s restore SMS message.

“SMS & Call reporting” tab

TrikdisConfig G17F System events window, SMS & Call reporting tab. For User 1, SMS is checked for the visible Low power, Power restore, Periodic test, RS485 device fault and restore, and GSM jamming and restore rows. Call is unchecked for all visible rows; SMS and Call are both unchecked for ESPA 4.4.4 text.

This window will only be displayed if at least one user phone number has been added to the „Users & Reporting“ window

  • ID – event’s number on the list and identification word (Event, Restore).

  • Event SMS text – text that will be included in SMS messages about events.

  • User SMS/Call – choose how to inform users about every event – via SMS message and/or call.

5.9 “Events Log” window

TrikdisConfig G17F Events Log window with Read Log and Clear Log buttons. The table lists Event No., Time, CID and Event definition; visible entries include Alarm in input IN5, System start and Configuration changed.

  • Read Log button – for reading the event log from the device’s memory.

  • Clear Log button – for clearing the event log entries from the device’s memory.

  • In the table, you can find the Event No., Time, CID code, Event definition. The events log can show up to 1000 events stored in the G17F’s memory.

5.10 Restore default settings

To restore the communicator’s default settings, click the TrikdisConfig button Restore.

TrikdisConfig Default settings section with the Restore button highlighted. The IMEI/Unique ID field and device status bar are visible.

6. Setting parameters remotely

Important

Remote configuration will only work when the G17F:

  1. Has an inserted and activated SIM card with the PIN code entered or disabled.

  2. Has Protegus service enabled. See 5.4 "Users & Reporting" window.

  3. Has the power switched on ("POWER" LED must be green solid);

  4. Is connected to a network (the "NETWORK" LED must be green solid and blink yellow).

If "NETWORK" is yellow solid or "DATA" is yellow solid, the device cannot connect to GSM and/or Protegus2.

  1. On your computer, launch the configuration software TrikdisConfig.

  2. In the Remote access window, enter the communicator’s Unique ID number. You can find this number on the back of the device and on the device’s packaging.

TrikdisConfig start window. In Remote access, the Unique ID field and Configure button are highlighted; the optional System Name field is beside Unique ID.

  1. (Optional) Enter a desired name for the communicator in the System Name field.

  2. Click Configure.

  3. In the window that opens, click Read [F4]. If prompted, enter the administrator or installer code.

  4. When you are finished setting the desired parameters, click Write [F5]. If you are done working with TrikdisConfig, click Disconnect.

7. Testing the G17F GSM communicator

When configuration and installation are complete, perform a system check:

  1. To test an input of the communicator, enable it. Check if the events were received by the Central Monitoring Station (CMS) and/or Protegus2 application.

  2. To test the communicator’s outputs, turn them on remotely and check their operation. Ensure that the events were received by the Central Monitoring Station (CMS) and/or Protegus2 application.

  3. Perform a fire alarm test to see if the CMS receives events correctly.

8. Updating firmware

Note

After connecting the communicator to TrikdisConfig, the program will automatically offer to update the firmware if any updates are available. Internet connection is needed for this feature. Antivirus software, firewall or strict internet access settings can block the automatic update feature.

The communicator’s firmware can also be updated or changed manually. All prior settings of the communicator remain after an update. If the firmware is installed manually, it can be changed to a newer or an older version. Perform these steps:

  1. Launch TrikdisConfig.

  2. Connect the communicator to the computer using a USB Mini-B cable or connect to the communicator remotely.

    • If a newer version of firmware is available, the program will automatically offer to install it.
  3. Open the TrikdisConfig window Firmware.

TrikdisConfig G17F Firmware window with an empty Open firmware file field, an Open firmware button, a disabled Update (F12) button and a progress bar at 0%.

  1. Click the button Open firmware and choose the required firmware file.

  2. Click the Update [F12] button.

  3. Wait for the update to finish.

9. Safety precautions

The communicator should be installed and maintained only by qualified personnel.

Please read this manual carefully prior to installation in order to avoid mistakes that can lead to malfunction or even damage to the equipment.

Always disconnect the power supply before making any electrical connections.

Any modifications, modernization or repairs not authorized by the manufacturer shall render the warranty void.

Crossed-out wheeled bin symbol (WEEE), indicating the device must be disposed of separately from household waste.Please adhere to your local waste sorting regulations and do not dispose of this equipment or its components with household waste.