Skip to content

Frequently Asked Questions

Answers to real questions that came up during installations, gathered from support cases. If your question isn't here, contact support@trikdis.lt.

FLEXi SP3

How do I set up a single Wiegand reader (no keypad) to pulse a door output?
  1. Wire the reader's data lines to the panel's GRN/YEL terminals.
  2. In TrikdisConfig, set Keypad type = Wiegand reader even though no physical keypad is connected ("Modules" window → "Keypads" tab → Keypad parameters).
  3. Give the target output Output definition = Remote control and a Pulse time, s (e.g. 5) in the "PGM" window.
  4. On the "PGM" window's "Control" tab, tick En for that reader, set PGM to the output number, and PGM mode = Pulse.

Note

RFID/Wiegand cards can't be enrolled by tapping the reader — enter each card's Tag code by hand, as a decimal number, under "Linking RFID key fobs (cards)".

See the FLEXi SP3 manual for full wiring diagrams and TrikdisConfig settings.